La. Admin. Code tit. 33, § XI-305 - Installation Requirements for Partially Deferred UST Systems
A. The requirements
in this Section apply to UST systems partially excluded under LAC
33:XI.101.C.1.a, b, and c.
B.
Owners and operators shall install a UST system listed in LAC 33:XI.101.C.1.a,
b, or c for the purpose of storing regulated substances (whether of single or
double-wall construction) that meets the following requirements.
1. The UST system will prevent releases due
to corrosion or structural failure for the operational life of the UST
system.
2. The UST system is
cathodically protected against corrosion, is constructed of noncorrodible
material or of metal clad with a noncorrodible material, or is designed in a
manner to prevent the release or threatened release of any stored
substance.
3. The UST system is
constructed or lined with material that is compatible with the stored
substance.
C.
Notwithstanding Subsection B of this Section, a UST system without corrosion
protection may be installed at a site that a corrosion expert determines is not
corrosive enough to cause the UST system to have a release due to corrosion
during its operating life. Owners and operators shall maintain records that
demonstrate compliance with the requirements of this Subsection for the
remaining life of the tank.
D. LAC
33:XI.599.Appendix A lists codes of practice developed by nationally-recognized
associations or independent testing laboratories that shall be used to comply
with these regulations.